ETCR085K Split Type Leakage Current Sensor
ETCR085K Split Type Leakage Current Sensor ETCR085K ETCR

Split CT Clamp: 85*20mm, Range: 0.000mA~60A(AC) Resolution:0.01mA, Current induction output, Direct Coil tap, Accuracy 1%, Four shielding, anti-jamming capability, suitable for leakage current and small current test.

ETCR085K Split Type Leakage Current Sensor
产品产商:
会员价格:0.00
服务:售前咨询电话:400-880-5151
如果您对该产品感兴趣的话,可以
ETCR085K Split Type Leakage Current Sensor

Ⅰ.Introduction

ETCR085K Clamp Type High Accuracy Leakage Current / Current Sensor is widely used in the field of electric power, communication, meteorology, railway, oil field, military, measuring, teaching research unit, industrial mining enterprises, etc, for measurement of AC leakage current, current, frequency, phase sequence, power and electrical energy. It can be connected with high accuracy digital multimeter, data recorder, electric power quality analyzer, oscilloscope, industrial control instrument, etc. It adopts open jaws design, with opening size of 85mm×20mm, very suitable for the place of flat steel ground connection. No need to take apart measured wires, which make the field testing and maintenance more secure and convenient. The combination of two sensors can be used as the sensor of non-contact ground resistance online testing.
ETCR085K Clamp Type High Accuracy Leakage Current / Current Sensor adopts the latest CT technology, multilayer shielding techniques, least affection from external magnetic field, and capable of waterproof, rainproof, drip tight to make sure the high precision, high stability and high reliability of perennial uninterrupted measurement. Meanwhile, customizing is acceptable to meet more use of different places.
 
Ⅱ.Technical Specifications
Function
High accuracy measurement of AC leakage current, current, frequency, phase sequence, power and electrical energy
Opening Type
Clamp type
Clamp Size
85mm×20mm
Coils Turn
1000 : 1
Input Range
AC 0.00mA~60.0A
Resolution
0.01mA
Induced Output
1mA/1A
Accuracy
±2%rdg±3dgt(23℃±5℃, below 80%RH)
Load Resistance
0mA~2000mA: ≤50Ω
0A~60A: ≤5Ω
Wire Identification
S1, S2---coil tap; GND---shield
Line Voltage
Below AC 600V line measurement
Overall Dimension
160mm×80mm×55mm
Weight
600g
Installation Direction
P1 side is upward
Installation Type
2 types
Working Temperature and Humidity
-20℃~50℃, below 80%rh
Storage Temperature and Humidity
-10℃~60℃, below 70%rh
Structure
Drip tight Ⅱ, rainproof
SafetySpecifications
IEC1010-1, IEC1010-2-032, 2 class of pollution, CAT Ⅲ(600V)
Accessories
Current Sensor: 1 pc; Connecting Bolt: 2 pcs; Connecting Nut: 2 pcs; Support: 4 pcs; Fixed Screw: 6 pcs.

III. Structure Drawing
ETCR085K Split Type Leakage Current Sensor

1. Fixing screw hole        2. Screws on wire connecting cover
3. Hole for installing against the wall (with accessories 8)     
4. Output lead wire interface       5. Fixing screw (2pcs)   
6. Hole for installing against the steel grounding wire (with accessories 9)
7. Shielding ground     8. Accessories for installing against the wall (4pcs)
9. Accessories for installing against the steel grounding wire (6pcs)
Copyright@ 2003-2019  Guangzhou ETCR Electronic Technology Co., Ltd..  All rights reserved.     

ETCR Electronic Technology Company

Add: No.8, Yongxing He Xingdong Street, Taihe Town,Baiyun District,Guangzhou,China. Tel: +86-020-62199556     Fax: +86-020-61100822   E-mail: info@etcr.cc