Products
Contact us

Sales: Lili Su (Ms.)
Tel: +86-020-62199556
Fax: +86-020-62199550
Mobile: (86)13802922567
E-mail: info@etcr.cc
Skype: etcr.info
QQ: 2850757785

MSN: etcr.sales@hotmail.com


简单介绍

 的详细介绍
ETCR6800D AC/DC Clamp Leaker
Color page: User's manual: CE certificate:
ETCR6800D AC/DC Clamp Leaker ETCR6800D ETCR

Use to measure AC/DC current, peaking hold on-line test. Measurement range: DC:0.0A~2000A, AC:0.0A~1500A. resolution:0.1A, size of clamp:Φ68mm.With USB interface and can upload data to pc, and can store 99sets data.

ETCR6800D AC/DC Clamp Leaker
产品产商:
会员价格:0.00
服务:售前咨询电话:400-880-5151
如果您对该产品感兴趣的话,可以
ETCR6800D AC/DC Clamp Leaker

 Introduction


ETCR6800D Clamp Meter is specially designed for measurement online of AC/DC leakage current with voltage below 600V; by adopting up-to-date CT technology and digital integration technology, There is not metallic conductor outside the clamps, non-contact test to ensure save. It is a product with relatively small size, large clamp, high accuracy and perfect function, widely applied in those fields as electricity, communications, meteorology, railroad, oilfield, construction, measurement, scientific & research teaching institutes, industrial and mining. It is essential tool for electrician safety testing. 

This High Accuracy Clamp Leaker have the function of peaking holding, data holding data storage; obtains one USB interface. With the help of the software that we provide, many functions are available. For example, the meter can realize on-line monitoring, historical data inquiry, active curve drawing, indication of max, min and average value and indication, alarm value setting, indication of alarm value, historical data inquiry, export, and print.

Ⅱ 
Technical Specifications
Function
 Measure AC/DC current, peak hold, online monitor
Size of clamp
 Φ68mm
Range
 DC:0.0A~2000A   AC:0.0A~1500A
Accuracy
 ±2%rdg±3dgt
Resolution
 0.1A
Dimension
 224mm×115mm×43mm
Data interface
 USB
Weight
 515g(with battery)
Power Supply
 Zn-Mn dry battery 6F22 9V, lasting for100hours
Test Mode
 Clip-on CT, noncontact mode
Display Mode
 Four digits LCD display
LCD Dimension
 35mm×21.5mm; display domain: 32mm×15mm
Frequency
 AC 45Hz~400Hz 
Sampling Rate
 2 times/s
Polarity Indication
 DC current auto identified and display“
Test Position
 Tested wire in the jaw center; Error will increase to 1.5%rdg max if deviate the center
Range Shift
 Automatically
Line Voltage
 AC600V
Software
 with the software the data can upload to computer
Data Memory
 99units, FULL blinks when the memory is full
Peak Hold
 Push HOLD without release, the meter will show the peak value during the pushing period
Reading Hold
 DH indicating the reading is hold
Out of Range
 OL indicating the current is out of range
Auto Power-off
 5 Minutes after power on, it will power off automatically to lower the power consumption
Battery Voltage
 Indicating the battery voltage is lower than 7.2V.Then the battery have to be changed
Consumption
 10mW
Temperature and Humidity
 -10℃~50℃; Below 80%rh
Max error refer to environment
 -10℃~0℃,40℃~50℃,Error will increase max to 1%rdg
Temperature and Humidity for storage
 -10℃~60℃,below 70%rh
Insulating Strength
 AC2kV/rms. (between the alloy of the clamp and the housing)
Applicable safety rules
 IEC1010-1, IEC1010-2-032, Pollution level 2, CAT Ⅲ(600V)
Accessories
 Meter: 1pc; USB communication line: 1pc; software: 1pc; battery (6F22 9V):1pc.

Ⅲ 
Field application
ETCR6800D AC/DC Clamp Leaker
Copyright@ 2003-2019  Guangzhou ETCR Electronic Technology Co., Ltd..  All rights reserved.     

ETCR Electronic Technology Company

Add: No.8, Yongxing He Xingdong Street, Taihe Town,Baiyun District,Guangzhou,China. Tel: +86-020-62199556     Fax: +86-020-61100822   E-mail: info@etcr.cc